Duplex Riser Door PF90

Duplex Riser doors provide vital fire protection to riser openings in multistorey buildings which have riser shafts running between floors. Our single leaf riser doors have been independently fire tested to 1 hours on both sides to ensure the spread of fire is contained on either side of the door. We make our Riser Doors in the UK to order.



Further Information

  • ❑  90 minute Fire Rated Riser Door, Maximum Size 2300 x 950mm
  • ❑   Tested to BS476: Part 22: 1987 (Minimum 90 mins in both directions )
  • ❑   Acoustic reduction of 36dB
  • ❑   Smoke Tested to EN 1634-3: 2004
  • ❑   Hinged on the long side.
  • ❑   25mm Picture frame
  • ❑   Fitted with 3 point locking mechanism operated by a steel "T-key"
  • ❑   A separate Euro Cylinder lock (not supplied) for additional security is available
  • ❑   Steel door and frame, powder-coated white (RAL9010 20% Gloss)
  • ❑   Manufactured with precision in Tamworth, UK


Stock Panel Sizes

NONE AVAILABLE - BESPOKE MADE TO ORDER ONLY



More Information

Fire Rated Access Panel with Picture frame

❑   1.5 Hour Fire Rated both sides - Tested to B.S.476: Part 22

❑   Complies with Part B Building Regulations

❑   Independently tested in a UKAS approved Test House and certified to a minimum 90 minute fire rating from both sides.


Material and Finish:

Frame: 1.2mm Zintec steel

Door: 0.9mm Zintec steel, door cavity filled with mineral wool insulation

Powder-coated in white RAL9010 with satin finish. This is a tough finish which is easy to wipe clean

Hinge: Zintect steel piano hinge


Lock options and locking:

Budget Lock - Features an 8mm square drive, opened with metal T-key.

Tamper Proof Lock and Euro Profile Lock Option available (See image gallery for comparison of the lock options)


The lock is a 90 degree turn lock which provides 3 locking points between the frame and the door.


Picture Frame Fire Rated Access Hatch Size information

Made to order tested up to 2300 x 950mm

Depth 75mm

25mm Picture frame


Fire test information

Tested to B.S.476: Part 22:1987 Both sides Test date 24th March 2022 Warrington Test N 507162



Insulated Meter Box Technical Drawing


Fitting instructions for Duplex 90 Range of Panels into wall.

Structural Opening to be formed, Level, Plumb, and Square.
Structural Opening should not exceed over 10mm from the Door/Frame Size

Example

1800mm x 600mm - The door and Frame require a Structural Opening.

1810mm x 610mm - Maximum.

Insert the Frame into the Structural opening.
Fix the frame using 75mm steel screws using the pre-punched holes on all four sides of the frame (do not fully tighten).
Ensure an equal gap around all sides of the frame (5mm maximum) using fire-rated packers where required.
Once packed out tighten all screws ensuring the frame remains square.
Ensure all fixings have a solid fix through the frame into the wall.
Apply Intumescent Sealant (4 Hour Fire Resistance) to fully seal the back edge of the frame/wall connection.
On larger doors, it is advised the door is removed from the frame by unbolting the door and lifting from the hinge studs.
Re-hang once the frame is fixed and secure, ensuring the gap is equal top and bottom before re-booting.

External Wall Insulation Electric Meter Box




LENGTH CONVERTER

Type a value in the Inches field to convert the value to mm:

mm

NEED FURTHER ASSISTANCE?

SHARE US

Instagram
Pinterest
MADE IN THE UK




Further Related products



Firepan PF60




MORE INFORMATION
Firepan BF60




MORE INFORMATION
Duplex Riser Door PF90




MORE INFORMATION
Duplex Riser Door PF120




MORE INFORMATION
Duplex Riser Door BF90




MORE INFORMATION
Duplex Riser Door BF120




MORE INFORMATION
Firepan Anti-Ligature PF60




MORE INFORMATION
Firepan Anti-Ligature BF60




MORE INFORMATION
Firepan Budget PF120




MORE INFORMATION
Firepan Budget BF120




MORE INFORMATION
Duplex Double Riser Door PF90




MORE INFORMATION
Duplex Double Riser Door BF90




MORE INFORMATION